Drop Hammer Exhaust Fan Retrofit for Textile Workshops
A textile workshop ventilation retrofit often begins with a practical constraint: the machines, the wall openings and the production schedule already exist. A new exhaust fan must remove excess heat without drawing replacement air through the wrong part of the building. Its shutters also need to open reliably during operation and close when a fan is switched off.
La página de DAIHO Extractor tipo martillo abatible features galvanized-steel construction, wall-mounted installation and automatic shutters. For factories with existing wall penetrations, buyers need to consider three key factors: whether the fan frame fits the opening, how staged fans interact and what installed airflow can be achieved.

Define the heat and air-quality problem first
Textile production areas generate heat from motors, drives and machinery, along with lint and dust from material handling. General exhaust fans help move room air and reduce heat accumulation when adequate outdoor replacement air is available. They are not a replacement for a properly designed dust-collection or local-exhaust system where airborne fibres or other contaminants need source capture.
Before modifying the existing fan arrangement, document the normal machine layout, existing fan openings, areas where operators report heat, doors used for makeup air and any dust extraction already installed. Note whether air quality, temperature or both are driving the retrofit. That distinction prevents you from specifying an oversized ventilation fan to solve what is really a dust-capture problem.
Which DAIHO drop-hammer fan model fits the wall?
The official product range lists several sizes. The following rows show how cabinet dimensions, power and published airflow change across the family. They are catalogue comparisons, not installed sizing recommendations.
|
Modelo |
Cabinet dimensions |
Published airflow / rated power |
|---|---|---|
|
DH(A)-900 |
900 × 900 × 400 mm |
28,000 m³/h / 0.37 kW |
|
DH(A)-1220 |
1,220 × 1,220 × 400 mm |
37,000 m³/h / 0.75 kW |
|
DH(A)-1380 |
1,380 × 1,380 × 400 mm |
44,500 m³/h / 1.1 kW |
|
DH(A)-1530 |
1,530 × 1,530 × 400 mm |
50,000 m³/h / 1.5 kW |
All models listed above use six-blade assemblies and are available in 380/220 V, 50 Hz configurations. Their published noise ratings range from 63 to 70 dB, depending on the model. Confirm the exact motor, voltage and option code on the quotation. The nominal fan size in the model label should not be confused with the impeller diameter or the finished wall opening.
Plan the wall opening and the airflow route together
A retrofit cannot be sized from floor area alone. Check the net opening width and height, structural support, wall thickness, outside service clearance and the obstruction created by racks, pipes or loading equipment. Make sure the exterior side provides enough space for the shutters to operate without hitting a grille, hood or adjacent structure.
Replacement air is equally important. If the exhaust wall is opposite the intended inlet, a crossflow route can serve the occupied area. If the nearest door becomes the only intake, air may short-circuit across a small section of the factory. Mark the intake and exhaust points on the same floor plan before selecting the number and location of fans.
Automatic shutters need a staged-operation check
The drop-hammer family uses automatic opening and closing shutters to limit backflow and weather entry. In a multi-fan workshop, one fan may run while adjacent units are off. The non-operating shutters should return to their closed position, while operating fans must open fully enough for the specified airflow. A sticking shutter adds resistance and can reduce useful air exchange.

During commissioning, start each fan stage individually and inspect the shutters from a safe position. Then operate the planned combinations and record any rattling, incomplete opening or reverse movement. Confirm that the control method, motor protection and electrical isolation are appropriate for the site. Never obstruct a running fan or enter the guard area to test shutter movement.
Compare wall-fan constructions for the actual environment
The drop-hammer unit is not the only wall-exhaust option in DAIHO’s rango de ventiladores de extracción de presión negativa. A fiberglass square exhaust fan has an FRP housing and PVC shutters that may suit a different corrosion or maintenance brief. The butterfly cone type exhaust fan uses a cone and double-door arrangement. Evaluate these configurations separately when material exposure, shutter sealing, or airflow performance is the deciding factor.
Do not assume that a cone, shutter or alternative casing automatically reduces energy use at the intended operating point. Ask for comparable fan performance data at the actual system resistance, and confirm the configuration being offered. Any claimed savings should reference a specific test or comparison basis.
Calculate operating cost from the duty, not from the fan count
Rated motor power is useful for an initial energy comparison, but electricity consumption also depends on runtime and control stages. For illustration, a DH(A)-1380 has a listed rated power of 1.1 kW. One unit operating for eight hours would represent 8.8 kWh using simple rated-power arithmetic; measured consumption can differ. This calculation illustrates energy estimation only—it does not determine the required fan quantity for a factory.
Before ordering, compare expected operating hours, available inlet area, room pressure, maintenance access and noise at nearby workstations. Multiple independently controlled fans may offer more flexibility than a single larger unit, but weigh this against the added installation and control complexity.
What a useful retrofit quotation should contain
Existing wall-opening measurements, permitted structural changes and the exact selected cabinet dimensions.
Target ventilation duty and the assumed system resistance, including inlet and shutter losses.
Model code, impeller and motor specification, voltage, controls, guards and shutter configuration.
The replacement-air path through the operating zones and interfaces with existing dust collection.
Maintenance access, cleaning responsibility and plans for inspecting shutters and the drive assembly.
Commissioning criteria for fan stages, shutter operation and ventilation performance at representative locations.
A successful retrofit delivers a clear path for replacement air and exhaust while fitting the existing building safely. Compare the fan’s listed rating with the actual opening, stage controls, shutters, and production layout before assuming the largest available model is necessary.
Preguntas frecuentes
Will a drop-hammer exhaust fan remove textile dust?
It can move airborne room air, but it is not a dust collector. Processes that generate hazardous or excessive fibres may require dedicated local extraction and filtration.
Why do the shutters matter when fans operate in stages?
Closed shutters limit reverse airflow through idle units. During operation, shutters must open properly to avoid unnecessary resistance and airflow loss.
Can the DH(A)-1380 replace an existing 1,380 mm fan without wall changes?
Not automatically. Check the finished opening, mounting details, external clearance, controls and performance duty; equal nominal dimensions do not guarantee a direct fit.
Is the highest published airflow the best retrofit choice?
No. Select the fan based on required room duty, installed pressure, replacement-air supply, and maintenance conditions.